Still more wiring questions

Home
Contact Us
Ask the Electrician
Products & Services
Project Portfolio
Dance of the Lights
About Us

There are multiple questions on this page. Be sure to scroll down and find the one you're looking for!

What do I need to do to operate a 480 volt 3-phase welder in my shop? I have 240 volts, single phase in there now.

If you have only 240v single phase in your building, you'll need to have a change in service installed to allow you to purchase a higher voltage from your electric company. They make phase converters that will produce 3-phase from single phase, but there's not much you can do if the voltage level you need (480volts) is less than what you have in the building without a service upgrade.

I turned on a lamp and the bulb blew out. Now I have no power on that outlet and three other ones. What happened?

Did the bulb definitely blow out? Did you try it on another receptacle?
Try plugging something else into the same receptacle and see if it works or not. If not, double-check that the breaker is on for sure.
Sometimes a breaker will trip and the handle doesn't move to the tripped position - turn it off and back on to reset it and make sure.
   
If all that doesn't make a difference, you may have a loose connection on one of the receptacles in the circuit which could be causing the other receptacles 'downstream' from it to lose power.

I have a 240 volt 3-phase motor that I want to connect to my three phase panel. Someone told me that I have to be careful when hooking up the high leg. Can you tell me what that’s about?

Three phase power comes in two different configurations- delta or wye. The configuration is determined by the utility company transformer that supplies your building. In a low voltage single phase application, the utility supplies you with 120 volts single pole or 240 volts two-pole. In a three phase application, your higher voltage depends on the configuration: 240 volts in a delta, or 208 volts in a wye. While most newer three phase devices will operate on a range of 208-240 volts and can be used on either a delta or wye system, some older equipment is rated for 230 to 240 volts and thus, can only be used in a three phase delta configuration system. When ordering 3-phase power, it’s important to check the power requirements of the equipment you intend to use before ordering the electric service.

Now, with regards to your high leg question, this has to do with the voltage measured between each single pole of a three phase  system and ground. In a wye system, you will measure 120 volts to ground on each pole, but 208 volts will be measured between any two poles. In a delta system, you will measure 120 volts to ground on two of the poles. The third pole will measure 240 volts to ground. But, you will measure 240 volts between any two poles.

The concern over the high leg only comes into play if you are connecting single pole loads to a three phase delta panel. In this case, it is important NOT to connect a single pole circuit breaker to the phase that measures 240 volts to ground or you will damage any devices connected to this circuit. For three-phase equipment, the high leg is not a concern since you are utilizing power over all three poles simultaneously. 
  
The same rules apply for higher voltage configurations (i.e. 277/480 volt systems, etc.) as with the low voltage example cited here.

I need a 220 volt circuit on the opposite end of my house from the panel. Do I have to run a new line, or can I use two existing 110 circuits somehow?

You would have to install a new circuit. It's not legal or safe to derive 220 volts from two separate and existing 110 volt circuits.

I need to add a GFCI outlet into an existing circuit but because of the location it would be difficult to add the additional outlet "in series." Rather, I'd like to tap into the existing circuit at a midpoint and wire the outlet in parallel with the existing wiring. Is there any problem with this?

Technically, all AC receptacles are wired in parallel. They may be 'daisy-chained' from one to the next, but there is no rule that says you have to add a new one at the end of the circuit - any point would do. Just be careful not to overload the capacity of the circuit you're connecting to.

Wurtsboro Electric Service, Inc.

Licensed electricians serving Orange county, Sullivan county, and Ulster county in New York
(845) 888-8000 

_________________________________________________________________________________________________ 
     
        
All information contained within this site ©2004-2016, Wurtsboro Electric Service, Inc. All rights reserved.
Reproducing or duplicating any information contained herein is prohibited by law.
Contact Us       About Us       Resources